August 14, 2026 - Patrick Kerwood

Graceful Shutdown on Power Loss with NUT and Proxmox

In this post, I’ll walk through configuring Network UPS Tools on a Proxmox host, from getting the UPS recognized over USB to triggering a clean shutdown after a set amount of time on battery, instead of waiting until the battery is nearly empty.

A UPS that nobody is listening to is just a battery that delays the crash. If the power is out longer than the battery lasts, the host still loses power mid-write, and on a hypervisor that means every running guest goes down hard.

Network UPS Tools solves this by monitoring the UPS and shutting the host down while there is still battery left. It is packaged in Debian, so it is available directly on Proxmox VE. The setup below uses an Eaton Ellipse ECO 1600 connected over USB, but the same steps apply to any UPS with a supported USB HID interface.

# How NUT Fits Together

NUT splits the work across three processes, which is why a single UPS ends up with five configuration files. Understanding the split makes the rest of this post much easier to follow.

  • The driver, usbhid-ups in our case, is the only component that talks to the hardware.
  • The server, upsd, takes the data from the driver and serves it over TCP port 3493.
  • The client, upsmon, connects to the server, watches the status and runs the shutdown when needed.

Data flows in one direction: UPS → driver → upsdupsmon → shutdown.

The important consequence is that upsmon is a network client even when it runs on the same machine as the UPS. It connects to upsd over localhost, which means it needs a username and password just like any remote client would. That credential pair is the piece most people trip over, so it is worth keeping in mind.

Each process has its own configuration file, all of them in /etc/nut.

  • nut.conf decides which processes run at all.
  • ups.conf configures the driver.
  • upsd.conf configures the server.
  • upsd.users holds the server’s accounts.
  • upsmon.conf configures the client.

# Installation

apt install nut nut-server nut-client

The Debian package ships with everything disabled by default, so nothing will run until the configuration is in place.

# Finding the UPS

Before touching any configuration, confirm the host actually sees the UPS.

lsusb

You are looking for a line identifying the UPS vendor. Eaton and MGE devices use vendor ID 0463.

Bus 002 Device 003: ID 0463:ffff MGE UPS Systems UPS

If nothing shows up, this is a hardware problem rather than a configuration problem. Watch dmesg -w while unplugging and replugging the cable.

On a Dell PowerEdge, also check System BIOS → Integrated Devices → User Accessible USB Ports, since setting it to Only Back Ports On will silently disable the front ports. Cheap or long USB cables are another common culprit, as UPS interfaces tend to be picky about them.

Once the device appears, nut-scanner will generate a ready-made driver configuration.

nut-scanner -U
[nutdev1]
	driver = "usbhid-ups"
	port = "auto"
	vendorid = "0463"
	productid = "FFFF"
	product = "Ellipse ECO"
	serial = "000000000"
	vendor = "EATON"

Note the serial number consisting entirely of zeros. That is a placeholder rather than a real serial, and matching on it can break after a reconnect, so leave it out of the configuration.

# Configuration

# /etc/nut/nut.conf

This file decides which NUT processes are allowed to start. Out of the box it is set to none, which is why both services will start and immediately exit with a message about adjusting the configuration.

MODE=standalone

Use standalone when the UPS is attached to this machine and only this machine monitors it. Use netserver if other hosts on the network should monitor the same UPS.

# /etc/nut/ups.conf

This configures the driver and gives the UPS an internal name, in this case eaton. That name is referenced later.

[eaton]
    driver = usbhid-ups
    port = auto
    vendorid = 0463
    productid = FFFF
    desc = "Eaton Ellipse ECO 1600"
    pollinterval = 5

You can verify the driver in the foreground before handing it over to systemd.

upsdrvctl -D start eaton

Look for a line naming the subdriver, for example Using subdriver: MGE HID 1.46. That confirms the device was properly recognized rather than falling back to a generic HID path. Stop it again afterwards with upsdrvctl stop, since systemd will manage the driver from here as nut-driver@eaton.service.

# /etc/nut/upsd.conf

With no LISTEN directive at all, upsd binds to localhost only, which is what you want for a standalone setup. If you plan to expose the UPS to something like Home Assistant, add the following instead.

LISTEN 0.0.0.0 3493

# /etc/nut/upsd.users

This is where the accounts live. The upsmon master line is a shorthand that grants exactly the permissions upsmon needs on the machine physically connected to the UPS. A second read-only account is useful if you want Home Assistant or a metrics exporter polling the UPS.

[upsmon]
    password = a-long-random-password
    upsmon master

[monuser]
    password = another-password
    upsmon slave

The distinction between master and slave only matters with multiple machines. The master is the host holding the USB cable, it shuts down last and cuts UPS power. Slaves just watch the status and shut themselves down.

# /etc/nut/upsmon.conf

Finally, tell the client which UPS to watch and which account to use. The password here must match upsd.users exactly.

MONITOR eaton@localhost 1 upsmon a-long-random-password master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POWERDOWNFLAG /etc/killpower

# Permissions

The configuration files contain plaintext passwords, so lock them down before starting anything.

chown root:nut /etc/nut/*.conf /etc/nut/upsd.users
chmod 640 /etc/nut/*.conf /etc/nut/upsd.users

# Starting and Verifying

systemctl restart nut-server nut-monitor
upsc eaton

You should get a list of variables back.

battery.charge: 100
battery.charge.low: 20
battery.runtime: 1668
ups.load: 18
ups.status: OL

If upsc returns a connection error, journalctl -u nut-server -u nut-monitor -u 'nut-driver@*' -n 30 will usually name the problem directly. A missing MODE in nut.conf and a mismatched password between upsd.users and upsmon.conf are the two most likely candidates.

Some log lines during startup look alarming but are harmless. A missing upsmon.pid on first start simply means no previous instance was running, and the upsnotify messages about systemd watchdog integration are cosmetic. NUT logs them once and moves on.

# Deciding When to Shut Down

Out of the box, upsmon waits for the UPS to report low battery before doing anything. On the setup above that means waiting until battery.charge.low of 20 percent.

To find out what that actually buys you, I pulled the mains plug and let the UPS run down. My server draws 18 percent of the Ellipse ECO 1600, which works out to roughly 180 watts, and at that load it lasted about 20 minutes before cutting power. That means the default policy leaves me somewhere around four minutes to stop every guest and halt the host once the low battery threshold is hit.

That may be enough. It may also not be, and the way to find out is to measure rather than guess.

time systemctl stop pve-guests

Run that, note the number, then start the guests again. A single VM that ignores ACPI shutdown requests can stretch this out considerably, and per-VM shutdown timeouts in the guest Options tab are worth setting for that reason.

If the margin looks thin, a better policy is to shut down after a fixed period on battery. Short outages and flickers are ignored entirely, and anything longer triggers a clean shutdown with most of the battery still in reserve. This is what upssched is for.

# /etc/nut/upsmon.conf

Add the notification hooks. upsmon already detects the on-battery and back-on-line events, these lines tell it to run a command in addition to logging them.

NOTIFYFLAG ONBATT	SYSLOG+EXEC
NOTIFYFLAG ONLINE	SYSLOG+EXEC
NOTIFYCMD /usr/sbin/upssched

# /etc/nut/upssched.conf

upssched is essentially a stopwatch. It starts a named countdown when the power fails and cancels it if the power comes back first.

CMDSCRIPT /usr/local/bin/upssched-cmd
PIPEFN /run/nut/upssched/upssched.pipe
LOCKFN /run/nut/upssched/upssched.lock

AT ONBATT * START-TIMER onbatt 600
AT ONLINE * CANCEL-TIMER onbatt

The pipe and lock paths are worth getting right. On Debian, /usr/lib/tmpfiles.d/nut-common-tmpfiles.conf creates /run/nut/upssched owned by nut:nut specifically for these files, so use that directory rather than /run/nut directly.

# /usr/local/bin/upssched-cmd

When a timer expires, upssched runs this script with the timer name as the first argument. The package ships an example at /usr/bin/upssched-cmd, but placing your own version under /usr/local/bin keeps it safe from being overwritten during a package upgrade.

#!/bin/sh
case $1 in
	onbatt)
		logger -t upssched-cmd "Timer expired: on battery too long, initiating shutdown"
		/sbin/upsmon -c fsd
		;;
	*)
		logger -t upssched-cmd "Unrecognized command: $1"
		;;
esac
chmod 750 /usr/local/bin/upssched-cmd
chown root:nut /usr/local/bin/upssched-cmd
systemctl restart nut-monitor

Note the use of upsmon -c fsd rather than calling shutdown directly. The fsd command runs SHUTDOWNCMD and also drops the killpower flag file, which tells the UPS to cut its output late in the shutdown sequence. That is what makes the UPS notice when mains power returns and cycle its outlets. Calling shutdown on its own halts the machine correctly but leaves it dark after the outage ends, which rather defeats the purpose.

# Testing

None of this is worth anything untested. Set the timer to something short while you verify the chain.

AT ONBATT * START-TIMER onbatt 30
systemctl restart nut-monitor
journalctl -f -t upssched-cmd -u nut-monitor

Now pull the mains plug. Within a few seconds you should see the on-battery notification, and 30 seconds later the log line from the script followed by the shutdown starting. If you would rather not shut the host down on the first attempt, comment out the upsmon -c fsd line so the script only logs, which proves the timer and script fire correctly.

Do a full end-to-end test eventually though. The part most likely to surprise you is whether the host actually powers back on once mains returns, and that only shows up in a complete run. Set the timer back to its real value afterwards.


Found a bug? Help me improve this page!